Analysis of VSC-based HVDC System under DC Faults

J. Rafferty*, D. J. Morrow, L. Xu

*Corresponding author for this work

Research output: Chapter in Book/Report/Conference proceedingConference contribution

13 Citations (Scopus)

Abstract

This paper analyzes the behavior of a Voltage Source Converter Based HVDC system under DC cable fault conditions. The behavior of the HVDC system during a permanent line-to-earth fault is analyzed, outlining the systems configuration and behavior at each stage of the fault timeline. Operation of the proposed system under a single earthing configurations i.e. Converter (solid) earthed/AC transformer unearthed, was analyzed and simulated, with particular attention paid to the converters operation. It was observed that the development of potential earth loops within the system as a result of DC line- toearth faults leads to substantial overcurrent and results in system configuration oscillation.
Original languageEnglish
Title of host publicationIECON 2013 - 39th Annual Conference of the IEEE Industrial Electronics Society
Place of PublicationNEW YORK
PublisherInstitute of Electrical and Electronics Engineers (IEEE)
Pages459-464
Number of pages6
DOIs
Publication statusPublished - 2013
Event39th Annual Conference of the IEEE Industrial-Electronics-Society (IECON) - Vienna, Austria
Duration: 10 Nov 201314 Nov 2013

Publication series

NameIEEE Industrial Electronics Society
PublisherIEEE
ISSN (Print)1553-572X

Conference

Conference39th Annual Conference of the IEEE Industrial-Electronics-Society (IECON)
CountryAustria
Period10/11/201314/11/2013

Keywords

  • DC Fault
  • HVDC
  • VSC
  • Wind Integration